Types of Circuit Breakers

Advertisements

Types of Circuit Breakers

[Based on Arc Quenching (Cooling) Media]

(1) ACB   : Air Circuit Breakers

(2) ABCB : Air Blast Circuit Breakers

(3) OCB   : Oil Circuit Breakers

(4) VCB    : Vacuum Circuit Breakers

(5)SF6CB: Sulphur-Hexa-Fluoride Circuit Breakers

Use = 3 Phase, 440V – Fitted in MSB / PDB

(6) MCCB: Moulded Care Circuit Breakers (100-1000A)

Use = 3 Phase, 440V – Fitted in MSB / PDB / Motor Switch Board / Battery Switch Boards

(7) MCB: Miniature Circuit Breakers (upto 100A)

Use = Single Phase, 220 V – Fitted in Lighting Switch Board

Short Circuit Fault – is said to have taken place when the current is not confined to its normal path of flow but diverted through alternate path(s)

Short Circuit Fault causes High Fault Current

This Short Circuit/High Fault Currents may result in excessive Thermal Stresses, Mechanical Stresses & Arcing leading to the damage of the electrical installation

Short Circuit Trip / Relay (Instantaneous)

It is used to protect the Generator / Equipment against Heavy Fault Current caused by a Short Circuit Fault

When Short Circuit Fault happens – this Trip / Relay Trips the Circuit Breaker – thus the Faulty Circuit (Generator / Equipment) is Isolated from the Supply

 

It consists of:

An Electromagnet (Iron Core surrounded

by a Current Coil (Load Current Coil))

An Armature (Trip Lever) held by a spring

 

When a Short Circuit happens:-

Short Circuit / Fault Current is produced

This Current flows through the Coil

A Magnetic Field is produced by the Electromagnet (Iron Core & Coil)

Electromagnet (acts as a Magnet) Pulls (Attracts) the Armature against the spring

When the Short Circuit / Fault Current is enough to pull the Armature against the Spring Force – A contact is made with the Trip Circuit

Circuit Breaker is tripped

(Old type electrical door bells use the similar mechanism – a circuit is made and broken several times to produce the buzzing sound)

Overload Trip / Relay

It is used to protect the Generator / Equipment against Overload (High Load Currents)

When Overload happens – this Trip / Relay Trips the Circuit Breaker – thus the Generator / Equipment is Isolated from the Bus Bar / Supply

 

An overload trip should not trip the Generator / Equipment –

If the increase in load is only for a short duration (momentary current Surge)

When the load is shared by an incoming generator

When high load motors are operated – high current is needed only during motor starting

 

Hence a Time Delay (15 seconds) is incorporated in the Trip/Relay – dashpot type trip

 

It consists of:

A Plunger and a Solenoid

Plunger is attached to a Piston

Piston has a small hole

Piston is placed in a Silicone Fluid

(viscosity does not vary with temperature)

Solenoid is connected to the Load Current

 

When Overload occurs / happens:

Load Current increases excessively

Plunger is attracted to the solenoid

Plunger / Piston moves upwards, as silicone fluid is displaced from top to bottom through the small hole in the piston

Time delay / lag depends upon hole size and viscosity of the silicone fluid

If the hole is big – time delay / lag is less and vice versa

Load Current Setting for Trip is about 25 % above maximum (but should not exceed 50 %)